16. Detailed Settings in EEPROM of Outdoor Unit
Never use the DN code unlisted in the following table.
4A Forced defrosting (SILENT pin action)
Condensation temperature adjustment
4E
Lower temperature of B area (Tc_B) for cooling mode
1
Condensation temperature adjustment
4F
Upper temperature of B area (Tc_B) for cooling mode
81
Outdoor unit capacity
8F High static pressure setting
A3 The minimum operating time 1 until defrosting
A6 Defrost fan speed select
A7 The minimum operating time 3 until defrosting
C1 O2 output change
CA The defrost detection temperture setting
Discharge air temperature control with thermostat
E1
OFF additional time
EF Indoor unit auto restart setting
0=Silent mode (P)
-7=-7°C
0=0°C (P) ,,,,,
(For detail, refer to 2-3-3)
-7=-7°C
0=0°C (P) ,,,,,
(For detail, refer to 2-3-3)
0=Invalid
1=22
4=32
5=36
8=50
9=56
12=80
13=90
16=125
17=140
20=200
21=224
533=42
25=355
28=500
29=560
32=670
33=710
0=Invalid (P)
2=Never use
4=Never use
6=Never use
20=20 minutes
40=40 minutes (P)
0=Invalid (P)
0=0 minute
90=90 minutes (P) ,,,,,
-1=Invalid
(For detail, refer to 3-4-3)
0=Continuously set OFF (P)
1=Refrigerant leak prevention (normal OFF)
2=Refrigerant leak prevention (normal ON)
3=Pumpdown control
(For detail, refer to 5-2)
-3=-3°C (P)
-9=-9°C ,,,,,
(For detail, refer to 3-4-3)
-20=-20 minutes
0=0 minute (P) ,,,,,
(For detail, refer to 9-5)
0=No control (P)
1=capable of auto restart
2=incapable of auto restart
(For detail, refer to 9-6)
1 - 24
Mini VRF SYSTEM
Control Functions
(P) : Factory preset mode
1=Forced defrosting
-6=-6°C ,,,,,
7=7°C
-6=-6°C ,,,,,
7=7°C
2=25
3=28
6=40
7=45
10=63
11=71
14=100
15=112
18=160
19=180
22=250
23=280
26=400
054=72
30=600
31=630
34=800
35=840
1=High static pressure mode
3=Never use
5=Never use
21= 21 minutes ,,,,,
41 - 90=Never use
1=LL fan speed
10=10 minutes ,,,,,
120=120 minutes
-6=-6°C
-30=-30°C
-19=-19 minutes ,,,,,
10=10 minutes