Panasonic U-4LE1E5 Service Manual page 66

Mini vrf system
Hide thumbs Also See for U-4LE1E5:
Table of Contents

Advertisement

1. Simple Settings Function
List of Simple Setting Items
Item code
Filter sign ON time
(filter life time)
Degree of filter fouling
Central control
address
Operating mode
priority change
Fan speed when
heating thermostat is
4
Heating intake
temperature shift
Electric heater
installation
Humidifying when
heater thermostat is
Change to remote
controller sensor
thermostat differential
Function of EXCT
(0B)
plug short-circuit
Permit/prohibit
(0D)
automatic
heating/cooling
Cool-only
NOTE
• In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF unless a
vaporizing humidifier is used.
• Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
• Do not change any setting data that does not appear in this list.
Item
No.
0000
Not displayed
0001
150 hours
0002
2,500 hours
0003
5,000 hours
0004
10,000 hours
0005
Use the filter clogging sensor.
0000
Standard (setting at time of shipping)
Highly fouled
0001
(Filter sign ON time is reduced to one-half the set time.)
0001
Central control address 1
0002
Central control address 2
0003
Central control address 3
0064
Central control address 64
0099
No central control address set (setting at time of shipping)
0000
Normal (setting at time of shipping)
0001
Priority
0000
0001
0002
OFF
0004
0005
0006
0000
No shift
0001
Shifts intake temperature 1°C down.
0002
Shifts intake temperature 2°C down.
0003
Shifts intake temperature 3°C down.
0004
Shifts intake temperature 4°C down.
0005
Shifts intake temperature 5°C down.
0006
Shifts intake temperature 6°C down.
0000
No heater
0001
Heater installed
0000
No (setting at time of shipping)
0001
Yes
OFF
0000
Thermostat OFF differential: − 1°C (setting at time of shipping)
0001
Thermostat OFF differential: − 0.5°C
0000
Indoor unit does thermostat OFF (factory preset mode)
0001
Indoor unit gives "P14" alarm and transmits the refrigerant leakage signal.
0000
Permit
0001
Prohibit
0000
Normal
0001
Cool only (Set "1" for item code OD.)
Setting data
Description
Compressor ON
Lo 1 min., LL 3 min.
Lo
LL
Lo 1 min., LL 3 min.
Lo
LL
4 - 4
Mini VRF SYSTEM
Remote Controller Functions
Compressor OFF
LL
LL
LL
Lo
Lo
Lo