PURON® (R-410A) QUICK REFERENCE GUIDE
• Puron® refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment andreplacement components
are designed to operate with Puron®.
• Puron® refrigerant cylinders are rose colored.
• Recovery cylinder service pressure rating must be 400 psig (2758 KPa) . DOT 4BA400 or DOT BW400.
• Puron® systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into
suction line with compressor operating.
• Manifold sets should be at least 700 psig (4826 KPa) high side and 180 psig (1241 KPa) low side with 550 psig (3792 KPa) low-side retard.
• Use hoses with 700 psig (4826 KPa) service pressure rating.
• Leak detectors should be designed to detect HFC refrigerant.
• Puron®, as with other HFCs, is only compatible with POE oils.
• Vacuum pumps will not remove moisture from oil.
• Do not leave Puron® suction line filter driers in line longer than 72 hrs.
• Do not use liquid-line filter driers with rated working pressures less than 600 psig (4137 KPa).
• Do not install a suction-line filter drier in liquid line.
• POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
• Poe oils may cause damage to certain plastics and roofing materials.
• Wrap all filter driers and service valves with wet cloth when brazing.
• A factory-approved liquid-line filter drier is required on every unit.
• Do not use an R-22 TXV.
• If indoor unit is equipped with an R-22 TXV, it must be changed to an Puron® TXV.
• All Puron® Heat Pumps must have indoor Puron® TXV.
• Never open system to atmosphere while it is under a vacuum.
• When system must be opened for service, recover refrigerant, break vacuum with dry nitrogen prior to opening to atmosphere. Evacuate to
500 microns prior to recharging.
• Always replace filter drier after opening system for service.
• Do not vent Puron® into the atmosphere.
• Do not use capillary tube coils.
• Observe all warnings, cautions, and bold text.
Copyright 2004 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
PC 101
Catalog No. 003-80011
Tab 5a 5a
Printed in U.S.A.
Form 38EYX-C1SI
38eyxc1si
Pg 12
11-03
Replaces: New

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents