Use: Setup Mode - GE On-line VH Series User Manual

Table of Contents

Advertisement

4.5

USE: SETUP MODE

The setup mode can only be entered if the UPS is in 'standby' -mode: connected to a live wall outlet and switched off (LED
'operation' blinks).
1
Press keypad 'O' and keep it pressed while pressing 'I' simultaneously. Release both buttons.
The setup sequence starts with the setup of the output voltage, indicated by a blinking LED 'operation'.
2
Scroll through the four functions with keypad 'I', one of the LEDs 'operation', 'on bypass', 'on battery' or 'alarm' will
blink, indicating which function has been selected (see fig. 4.5).
3
Toggle the setting of the selected function by pressing switch 'O'. The LEDs on the LED bar 'runtime capacity' shows
the setting.
4
Store the new settings and leave the setup mode: press keypad '0' and keep it pressed while pressing 'I'
simultaneously. Release both buttons.
Output voltage
Phase – Neutral
*DEFAULT SETTING
Modifications reserved
GE_UPS_OPM_VHU_208_2K0_3K0_XUS_V010.docx
Bypass
reversal
Output
frequency
Fig. 4.5: Setup menu
Critical Power
208 Vac*
220 Vac
enabled*
disabled
disabled*
enabled
auto*
50 Hz
230 Vac
240 Vac
60 Hz
Operating Manual VH2000-3000 208V UL
Page 17/22