3.3

REAR PANEL

Figure 3.3 shows the rear panel of the VH2000/3000 208V.
The differences between the VH2000 and VH3000 are clearly indicated in the text below.
1
Input plug
AC mains supply to the UPS
Type: NEMA L6-20P
VH2000 208V: max. rating 10.4A
VH3000 208V: max. rating 15.2A
2
Input thermal circuit breaker: 20A
Protects the UPS from damage caused by
high input currents
3
Appliance outlets
To connect the loads to the UPS.
Type: NEMA 6-20R
VH2000 208V: rating 9.7A
VH3000 208V: rating 14.5A
4
Appliance outlets
To connect the loads to the UPS.
Type: NEMA L6-20R
VH2000 208V: rating 9.7A
VH3000 208V: rating 14.5A
5
DC connector
To connect a battery extension pack for
extended battery runtime
6
Fan(s)
Electronically controlled cooling fan(s).
Make sure ventilation air can move freely
around and through the UPS.
7
USB port
See 5.1 for more information
3.4
INSTALLATION & CONNECTIONS
3.4.1

Preparation

Mount the front panel that came with the UPS
to the unit by simply pressing, as shown in
figure 3.4.1.
3.4.2

Connecting interface devices

If you do not want to use the communication
capabilities of the UPS, please skip this
section and proceed with 3.4.3.
The UPS is equipped with two interface ports: a
USB port and an RJ11 port, allowing advanced
communication between the UPS and a
computer (network). Refer to section 5 for
more detailed information.
Modifications reserved
GE_UPS_OPM_VHU_208_2K0_3K0_XUS_V010.docx
Critical Power
7
5
3
4
Fig. 3.3: Rear panel VH2000/3000 208V
8
RJ11 port
See 5.2 for more information
Fig. 3.4.1: Mounting front panel
6
9
REPO
(Remote Emergency Power OFF)
Operating Manual VH2000-3000 208V UL
8
9
1
2
Page 8/22