Connecting REPO (Remote Emergency Power Off) switch

REPO can be used to remotely shut down the UPS using the connector provided on the rear panel of the UPS (9, fig. 3.3).
Figure 3.4.4 shows all suitable connections on the REPO Connector.
1. Remove the cable link from the male connector that came with the unit
2. Connect a switch to the male connector, the switch should be of Normally Closed type for normal operation.
3. Place the male connector to the connector on the rear panel of the UPS (9, fig. 3.3.)
4. When the switch is opened, the UPS will shut down. More information is given in section 4.4.14.
WARNING!
The REPO Contact is a Safety Extra Low Voltage Circuit. Connect it only to a SELV Circuit.
NOTE
Use standard Low Voltage Cable in accordance with National and local regulations.
Fig. 3.4.4: REPO connections
Modifications reserved
GE_UPS_OPM_VHU_208_2K0_3K0_XUS_V010.docx
Critical Power
NOTE
To maintain the security of the SELV circuit be sure to use the following
(only for qualified, skilled and service personnel) :
Wire type: UL Style 1015, 86°F (10°C), 600 VAC
Minimum wire: AWG 26
Maximum wire: AWG 16
Torque: 3.0 lb-inch