Advertisement

4. Configure Zones Submenu
5.6
See section 3.3.7 Configure Zones Submenu for more detail
Definitions:
Zone – Defines Sensor Input & Relay / Alarm Output
Group – Set of Sensors of same type and output within the same zone.
Average – Activation based upon an average of sensors in a group
Voting – Number of sensors needed to be above trip point to activate output
Quorum – Number of sensors need to vote, 1 = any sensor.
Press Menu to display Hardware Summary
x 4 Configure Zones
 Zone 1 Controls
R_ R_ R_ H_ S_
Enter (underlined) number of output for zone
R = Relay (1, 2 and 3), H = Horn (4), S = Strobe (5)
 Configure Group 1
Sensor type - enter #
1=CO, 2=NO2, 3=Combustible, 0=None
 Sensor Number - enter a two digit number for each sensor to be included in the group (e.g., 01, 02, 03...12.) from 01 through 12.
 Rising (activation) Trip point
The default rising trip points are:
Carbon
Description
Monoxide
Type
CO
Rising Level
35ppm
Z o n e
1
R 1
R 2
Figure A-21 Zone Controls
Z 1
G r o u p
S e n s o r
Figure A-22 Zone Group Type
Z 1
G r o u p
S e n s o r s : 0 2 , 0 4 , 1 1
Figure A-23 Sensor Selection
Z 1
G r o u p
R i s i n g :
Figure A-24 Rising Trip Point Entry
Nitrogen
Combustible
Dioxide
Gas
NO2
EX
2.5ppm
10%
C o n t r o l s
R 3
H 4
S 5
1
N O 2
T y p e : 2
1
N O 2
1
N O 2
2 . 5 p p m
Hydrogen
Ammonia
Sulfide
NH3
H2S
25ppm
8ppm
46
Carbon
Refrigerants
Dioxide
REF
CO2
100ppm
1000ppm
Oxygen
O2
20.3%