Group 2 in each zone
Group 3 in each zone
Group 4 in each zone
Group 5 in each zone
Group 6 in each zone
Group 7 in each zone
Group 8 in each zone
Carbon
Description
Monoxide
Type
CO
Range
200 ppm
Alarm Level
200ppm
Warning Level
100ppm
Rising Level
35ppm
Falling Level
15ppm
Typical coverage for CO, CO2 and NO2 sensors is 5,000 sq. ft. (464.5 sq. m), 900 sq. ft. (83.6 sq. m) for combustibles and other toxic
gases (see the User Instructions of each sensor type for location and coverage details). Extra sensors may be needed near areas
where people work, such as toll booths. Macurco provides only the control panels and sensors. Fans, relays, and other devices are
provided by the contractor. See the appropriate building code for the size of fans and air changes per unit of time.
.
Type 2 NO2, Voting mode, Quorum = 1
Type 3 EX, Voting mode, Quorum = 1
Type 4 NH3, Voting mode, Quorum = 1
Type 5 H2S, Voting mode, Quorum = 1
Type 6 REF, Voting mode, Quorum = 1
Type 7 CO2, Voting mode, Quorum = 1
Type 8 O2, Voting mode, Quorum = 1
Nitrogen
Combustible
Dioxide
Gas
NO2
EX
20 ppm
50%
5ppm
20%
3ppm
15%
2.5ppm
10%
1.2ppm
5%
Figure A-1 System Wiring Diagram
Hydrogen
Ammonia
Sulfide
NH3
H2S
100 ppm
50ppm
75ppm
20ppm
50ppm
14ppm
25ppm
8ppm
10ppm
3ppm
41
Carbon
Refrigerants
Dioxide
REF
CO2
1000 ppm
5,000ppm
300ppm
3,000ppm
200ppm
2,000ppm
100ppm
1,000ppm
50ppm
800ppm
Oxygen
O2
25%
19.5%
20.0%
20.3%
20.6%