Macurco DVP-120 User Instructions page 24

Detection and ventilation control panel
Table of Contents

Advertisement

"Depletion" is "1" when the sensor is a depletion type and "0" when it is not a depletion type sensor. A depletion sensor detects when
gas concentrations in a space fall below a specified level.
"Dec." defines how many decimal points are used to display the reading, alarm, warning, range, rising and falling levels. It can have
values between 0 and 2.
"Res." Defines the resolution used to display the reading, alarm, warning, range, falling level and rising level. It can have values
between: 1 and 500 when "Dec." is 0, 50.0 when "Dec." is 1 and 5.00 when "Dec." is 2.
"Range" is the value displayed when current measured is 20mA.
"Alarm" is the default alarm range.
"Warn" is the default warning range.
"Rise" is the default rising level used in Zone configuration.
"Fall" is the default falling level used in Zone configuration.
T y p e : 0 1
D e p l e t i o n : 0 N o
Figure 3-21.6 Depletion Type
T y p e : 0 1
D e c . : 0 8 8 8 8 . p p m
Figure 3-21.7 Decimal Points
T y p e : 0 1
R e s . :
1 p p m
Figure 3-21.8 Resolution
T y p e : 0 1
R a n g e :
2 0 0 p p m
Figure 3-21.9 Sensor Range
T y p e : 0 1
A l a r m :
2 0 0 p p m
Figure 3-21.10 Alarm Level
T y p e : 0 1
W a r n :
1 0 0 p p m
Figure 3-21.11 Warning Level
T y p e : 0 1
R i s e :
3 5 p p m
Figure 3-21.12 Rising Trip Point
T y p e : 0 1
F a l l :
1 5 p p m
Figure 3-21.13 Falling Trip Point
24
C O
C O
C O
C O
C O
C O
C O
C O