Relay Minimum On Time; Configure Horn Submenu; Horn Summary; Horn Turn On Delay - Macurco DVP-120 User Instructions

Detection and ventilation control panel
Table of Contents

Advertisement

The default turn on delay is one minute and the maximum allowed value is fifteen minutes. The value is entered in two groups, 2 digits
for the minutes and then 2 digits for the seconds. A leading zero must be entered for each group if applicable.
3.3.4.4

Relay Minimum On Time

The default minimum on time is one minute and the maximum allowed value is fifteen minutes.
3.3.5

Configure Horn Submenu

The configuration parameters for the horn are similar to those for relays. A horn would not normally require a minimum on time but this
parameter allows a more versatile configuration.
3.3.5.1

Horn Summary

This display example shows that the horn has been configured to operate with a turn on delay and no minimum on time.
Notice that the horn number, 4, is underlined. This indicates that the digit keys can be used to jump to a particular relay, horn or strobe.
The relays are numbers 1, 2 and 3; the horn is number 4 and the strobe is 5.
3.3.5.2

Horn Turn On Delay

The default turn on delay is one minute and the maximum allowed value is fifteen minutes.
3.3.5.3

Horn Minimum On Time

The default minimum on time is zero and the maximum allowed value is fifteen minutes.
3.3.6

Configure Strobe Submenu

The configuration parameters for the strobe are the same as those for relays. A strobe would not normally require a minimum on time
but this parameter allows a more versatile configuration.
3.3.6.1

Strobe Summary

This display example shows that the strobe has been configured to operate with a turn on delay and no minimum on time.
R e l a y
1
( m m : s s )
Figure 3-33 Minimum on time
H o r n
4
D e l a y
O n
Figure 3-34 Horn Summary
H o r n
( m m : s s )
Figure 3-35 Horn Turn On Delay
H o r n
( m m : s s )
Figure 3-36 Horn Minimum on time
S t r o b e 5
D e l a y
O n
Figure 3-37 Strobe Summary
M i n . O n
0 1 : 0 0
D e l a y
O n
0 1 : 0 0
M i n . O n
0 0 : 0 0
28