Load Default Configuration; Change Password - Macurco DVP-120 User Instructions

Detection and ventilation control panel
Table of Contents

Advertisement

3.3.2.3

Load Default Configuration

When the number one (1) digit is pressed, the panel will prompt for the password, even if it has been entered previously. If the
password is entered correctly, the panel will overwrite the existing configuration with the default configuration. This operation is
intended to restore the panel to a known basic condition if it is removed from one installation and installed in another.
The default configuration is:
Password
Sensors
Alarm signals
Warning signals
Trouble signals
Relay 1
Relay 2
Relay 3
Horn
Strobe
Zone1
Zone2
Zone3
Group 1 in each zone
Group 2 in each zone
Group 3 in each zone
Group 4 in each zone
Group 5 in each zone
Group 6 in each zone
Group 7 in each zone
Group 8 in each zone
Carbon
Description
Monoxide
Type
CO
Range
200 ppm
Alarm Level
200ppm
Warning Level
100ppm
Rising Level
35ppm
Falling Level
15ppm
3.3.2.4

Change Password

When the first digit is entered to change the password the panel will prompt for the existing password to be entered (if it hasn't already
been entered), see section 3.3.2.5 for more detail. Once the current password has been entered, the panel will prompt for the new
password.
1
L o a d
C o n f i g u r a t i o n
Figure 3-20 Load Default Configuration
1234
Undefined
Buzzer = Intermittent, Horn = Intermittent, Strobe = Continuous
Buzzer = Off, Horn = Off, Strobe = Off
Buzzer = Triple Tap, Horn = Off, Strobe = Off
Normally off, 1 minute turn on delay, 1 minute minimum on time
Normally off, 1 minute turn on delay, 1 minute minimum on time
Normally off, 1 minute turn on delay, 1 minute minimum on time
Normally off, 1 minute turn on delay, 0 (zero) minimum on time
Normally off, 1 minute turn on delay, 0 (zero) minimum on time
Controls R1,
Controls R2,
Controls R3
Type 1 CO, Voting mode, Quorum = 1
Type 2 NO2, Voting mode, Quorum = 1
Type 3 EX, Voting mode, Quorum = 1
Type 4 NH3, Voting mode, Quorum = 1
Type 5 H2S, Voting mode, Quorum = 1
Type 6 REF, Voting mode, Quorum = 1
Type 7 CO2, Voting mode, Quorum = 1
Type 8 O2, Voting mode, Quorum = 1
Nitrogen
Combustible
Dioxide
Gas
NO2
EX
20 ppm
50%
5ppm
20%
3ppm
15%
2.5ppm
10%
1.2ppm
5%
C h a n g e
Figure 3-21 Change Password
D e f a u l t
Hydrogen
Ammonia
Sulfide
NH3
H2S
100 ppm
50ppm
75ppm
20ppm
50ppm
14ppm
25ppm
8ppm
10ppm
3ppm
P a s s w o r d
* * * *
22
Carbon
Refrigerants
Dioxide
REF
CO2
1000 ppm
5,000ppm
300ppm
3,000ppm
200ppm
2,000ppm
100ppm
1,000ppm
50ppm
800ppm
Oxygen
O2
25%
19.5%
20.0%
20.3%
20.6%