Zone Group Type; Timed Day Selection - Macurco DVP-120 User Instructions

Detection and ventilation control panel
Table of Contents

Advertisement

The digit controls are:
1
2
3
4
5
When controlled by a zone the default horn pattern is the Triple Tap pattern, see 3.3.8.7 and the strobe will turn on continuously when
a zone is controlling them.
Each zone can have up to three control groups defined. Each group either monitors a sensor type or implements a timer function.
3.3.7.2

Zone Group Type

This display example shows that group 1 in zone 1 will be monitoring Nitrogen Dioxide sensors. The valid Types are:
0
1
2
3
4
5
6
7
8
The default Types are:
Group 1 in each zone
Group 2 in each zone
Group 3 in each zone
Group 4 in each zone
Group 5 in each zone
Group 6 in each zone
Group 7 in each zone
Group 8 in each zone
Timed mode turns the zone's outputs on at the START TIME if the current day is a weekday (or a weekend) and turns them off at the
next occurrence of STOP TIME. The other three modes turn the outputs on if the gas concentration indicated by that type of sensor is
at or above the Rising Trip Point and turns the outputs off if the concentration is less than or equal to the Falling Trip Point.
3.3.7.3

Timed Day Selection

Valid entries are:
1 Weekdays, Monday thru Friday, (default)
2 Weekends, Saturday and Sunday
Relay 1 added/removed from the zone's control
Relay 2 added/removed from the zone's control
Relay 3 added/removed from the zone's control
Horn added/removed from the zone's control
Strobe added/removed from the zone's control
Z 1
G r o u p
S e n s o r
Figure 3-41 Zone Group Type
Timed
Carbon Monoxide (CO)
Nitrogen Dioxide (NO2)
Combustible (EX)
Ammonia (NH3)
Hydrogen Sulfide (H2S)
Refrigerants (REF)
Carbon Dioxide (CO2)
Oxygen (O2)
Type 1 CO, Voting mode, Quorum = 1
Type 2 NO2, Voting mode, Quorum = 1
Type 3 EX, Voting mode, Quorum = 1
Type 4 NH3, Voting mode, Quorum = 1
Type 5 H2S, Voting mode, Quorum = 1
Type 6 REF, Voting mode, Quorum = 1
Type 7 CO2, Voting mode, Quorum = 1
Type 8 O2, Voting mode, Quorum = 1
Z 1
G r o u p
D a y s : 1
Figure 3-42 Timer Days Selection
1
N O 2
T y P e : 2
1
T i m e d
W E e k d a y s
30

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dvp-120m

Table of Contents