Macurco DVP-120 User Instructions page 44

Detection and ventilation control panel
Table of Contents

Advertisement

When the first digit is entered, the panel will appear as follows:
If the password is not entered correctly the panel will display as follows:
Once the current password has been entered, the panel will prompt for the configuration parameter being changed.
If the password has been lost:
1. Power down the DVP-120
2. Remove the Jumper Shorting Connector from the EXT header and place the Jumper Shorting Connector onto
the top two pins of the SYS header.
3. Power up the DVP-120. The first display is the current password on the unit.
4. Remove the Jumper Shorting Connector from the SYS header and install back onto the two bottom pins of the
EXT header.
2. Configure Sensors Submenu
5.1
See section 3.1 Initial Operating Mode for more detail
5.2
See section 3.1.2 User Interface for more detail
5.3
See section 3.3 Setting the System Configuration for more detail
5.4
See section 3.3.3 Configure Sensors Submenu for more detail
Press Menu to display Hardware Summary
 x 2 Configure Sensors
 Sensor
 Sensor type (set sensor type)
1=CO, 2=NO2, 3=EX, 4=NH3, 5=H2S, 6=REF, 7=CO2, 8=O2 and 0=None
 Alarm Level - set level if needed, 0 = disable
E n t e r
P a s s w o r d
_ _ _ *
Figure A-10 Password Prompt
W r o n g
P a s s w o r d
Figure A-11 Wrong Password Prompt
S e n s o R
0 1
A :
2 0 0
Figure A-12 Sensor Summary
S e n s o r
0 1
T y p e : 1
Figure A-13 Sensor Type
S e n s o r
0 1
A l a r m :
Figure A-14 Sensor Alarm Level
C O
W :
5 0
C O
C O
2 0 0 p p m
44