Analogue Outputs (Control Panel: Menu Par -> P9) - Vacon 20 Complete User's Manual

Ac drives
Hide thumbs Also See for 20:
Table of Contents

Advertisement

84
vacon
8.10 Analogue outputs (Control panel: Menu PAR -> P9)
Code
Parameter
Analog output
i
P9.1
signal selection
Analog output
i
P9.2
minimum
Analog output
P9.3
scaling
Analog output fil-
P9.4
ter time
Analog output E1
P9.5
signal selection
Analog output E1
P9.6
minimum
Analog output E1
P9.7
scaling
Analog output E1
P9.8
filter time
Table 8.10: Analogue outputs
8
Min
Max
Unit Default ID
0
14
0
1
0,0
1000,0
%
100,0
10,00
s
0,00
14
0
1
0
0,0
1000,0
%
100,0
0,00
10,00
s
parameters
Selections
0 = Not used
1 = Output freq. (0-f
2 = Output current (0-I
3 = Motor torque (0-T
4 = PID output (0 - 100%)
5 = Freq. refer. (0-f
6 = Motor speed (0-n
7 = Motor power (0-P
8 = Motor Voltage (0-U
1
307
9 = DC-link Voltage
(0 - 1000 V)
10 = Process Data In1
(0 - 10000)
11 = Process Data In2
(0 - 10000)
12 = Process Data In3
(0 - 10000)
13 = Process Data In4
(0 - 10000)
14 = Test 100%
0 = 0 V / 0 mA
0
310
1 = 2 V / 4 mA
311 Scaling factor
0,10
308 Filter time
As parameter P9.1, hidden
0
472
until an option board is con-
nected
As parameter P9.2, hidden
0
475
until an option board is con-
nected
As parameter P9.3, hidden
476
until an option board is con-
nected
As parameter P9.4, hidden
0,10
473
until an option board is con-
nected
)
max
)
nMotor
)
nMotor
)
max
)
max
)
nMotor
)
nMotor

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents