Installing The Outdoor Unit; Bleeding - Vivax ACP-24COFM70GEI User Manual

Hide thumbs Also See for ACP-24COFM70GEI:
Table of Contents

Advertisement

INSTALLING THE OUTDOOR UNIT

Location
Use bolts to secure the unit to a flat, solid floor.
When mounting the unit on a wall or the roof, make
sure the support is firmly secured so that it cannot
move in the event of intense vibrations or a strong
wind.
Do not install the outdoor unit in pits or air vents
Installing the pipes
Use suitable connecting pipes and equipment for the
refrigerant R410A.
The refrigerant pipes must not exceed the maximum
lengths 10m.
Wrap all the refrigerant pipes and joints.
Tighten the connections using two wrenches working
in opposite directions.

BLEEDING

Humid air left inside the refrigerant circuit can cause com-
pressor malfunction. After having connected the indoor
and outdoor units, bleed the air and humidity from the
refrigerant circuit using a vacuum pump.
(1) Unscrew and remove the caps from the 2-way and 3-
way valves.
(2) Unscrew and remove the cap from the service valve.
(3) Connect the vacuum pump hose to the service valve.
(4) Operate the vacuum pump for 10-15 minutes until an
absolute vacuum of 10 mm Hg has been reached.
(5) With the vacuum pump still in operation, close the
low-pressure knob on the vacuum pump coupling. Stop
the vacuum pump.
(6) Open the 2-way valve by 1/4 turn and then close it
after 10 seconds. Check all the joints for leaks using
liquid soap or an electronic leak device.
(7) Turn the body of the 2-way and 3-way valves. Discon-
nect the vacuum pump hose.
(8) Replace and tighten all the caps on the valves.
Diameter (mm)
ø 6
ø
9.52
ø
16
ø
12
ø
19
12K unit need to be installed the indoor unit
connection pipe with the "conversion joint"
12
6
Twisting moment (N.m)
15-20
35-40
60-65
45-50
70-75
Install the drain fitting and the drain hose (for
model with heat pump only)
Condensation is produced and flows from the outdoor unit
when the appliance is operating in the heating mode. In order
not to disturb neighbours and to respect the environment,
install a drain fitting and a drain hose to channel the conden-
sate water. Install the drain fitting and rubber washer on the
outdoor unit chassis and connect a drain hose to it as shown
in the figure.
Vacuum pump
INDOOR
UNIT
Refrigerant fluid direction of flow
3-way valve
(7) Turn to open fully
Service
inlet
(2) Turn
(8) Secure
Valve cap
12K MODE:
INSTALLER
INSTALLER
Vacuum pump
Pompa a vuoto
2-way valve
(6) Open by 1/4 turn
(7) Turn to open fully
Valve cap
(2) Turn
(8) Secure
(2) Turn
(8) Secure
Connect to the
indoor unit
conversion joint

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acp-28cofm80gei

Table of Contents