(2) Correcton by refrgerant ppng length
(2)-1 S seres
(2)-1-1 Heatng capacty correcton
PUMY-P100,125,140VHMB/P100,112,125,140YHMB
1.00
0.95
0.90
0
20
Piping equivalent length (m)
(2)-1-2 How to obtain the equivalent piping length
1. PUMY-P100, 125, 140VHMB/PUMY-P100, 112, 125, 140YHMB
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.3 × number of bends in the piping) m