Cmb-P104V-G1 - Mitsubishi PWFY-P100VM-E-BU Data Book

Hide thumbs Also See for PWFY-P100VM-E-BU:
Table of Contents

Advertisement

(4) CMB-P104V-G1

Model
Number of branch
Power source
Power nput
Coolng
(220/230/240)
Heatng
Current
Coolng
(220/230/240)
Heatng
External finish
Connectable outdoor unit/heat source unit
Indoor unit capacity
connectable to 1 branch
External dimension H x W x D
Connectable outdoor unit/heat source unit
Refrgerant
ppng
capacty
diameter
Field drain pipe size
Net weght
Accessores
Remark
Note:
*1. Installation/foundation work, electrical connection work, insulation work, power source switch, and other items shall be referred to the Installation Manual.
*2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
*4. Indoor units P100, P125, P140 can be connected to 1 branch. (In this case, cooling capacity decrease a little.)
*5. Refrigerant piping diameter for connection of plural indoor units with 1 branch shall be referred to the Installation Manual.
(5) CMB-PW202V-J
Model
Number of branch
Power source
Power input
Current
External finish
Connectable outdoor unit/heat source unit
Connectable unit capacity
External dimension H x W x D
Refrigerant
To
piping
outdoor unit
diameter
/heat source
High press. pipe
unit
Low press. pipe
To
indoor/
PWFY unit
Liquid pipe
Gas pipe
Field drain pipe size
Net weight
Accessories
Note:
*1. For installation/foundation work, electrical connection work, insulation work, and power source switch etc., refer to the Installation Manual.
*2. The equipment is for R410A refrigerant.
*3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the Water system Connection Box at least 5m away from any indoor units.)
*4. Install the unit horizontally.
*5. The indoor / PWFY unit branch is for cooling / heating. The indoor / PWFY unit cannot be simultaneously operated in different operation modes.
*6. The PWFY unit branch is for the heating only.
*7. Seal the unused branch using the optional cover cap (CMY-S202-J).
*Other models of BC controller are available. For unit information, refer to the Data Book.
0.067/0.076/0.085
kW
0.030/0.034/0.038
0.31/0.34/0.36
A
0.14/0.15/0.16
( Use optional joint pipe combing 2 branches when the total unit capacity exceeds 81. )
mm (in.)
High press. pipe
15.88 (5/8)
to P200
mm (in.) O.D.
P250/P300
19.05 (3/4)
mm (in.) O.D.
19.05 (3/4)
to P350
mm (in.) O.D.
Liquid pipe
Indoor unit Model 50 or smaller 6.35 (1/4) Brazed
mm (in.) O.D.
bigger than 50 9.52 (3/8) Brazed
(12.7 (1/2) with optional joint pipe used.)
mm (in.) O.D.
kg (lbs)
kW
Cooling : 0.019/0.020/0.021
Heating : 0.020/0.022/0.024
A
Cooling : 0.09/0.09/0.09
Heating : 0.10/0.10/0.10
Total
Indoor / PWFY
branch
PWFY branch
mm(in.)
P200
mm(in.)
ø15.88 (ø5/8" ) Brazed
ø19.05 (ø3/4" ) Brazed
mm(in.)
~P140
mm(in.)
ø9.52 (ø3/8" )
Brazed
mm(in.)
ø15.88 (ø5/8" )
Brazed
kg(lbs)
- 6 -
CMB-P104V-G1
4
1-phase 220/230/240V
50Hz
Galvanized steel plate
(Lower part drain pan painting N1.5)
PURY-(E)P200/250/300/350YJM-A(-BS)
PQRY-P200/250/300YHM-A
Model P80 or smaller
284 x 648 x 432 (11-3/16 x 25-17/32 x 17-1/32)
To outdoor unit/heat source unit
Brazed
Brazed
Brazed
To indoor unit
Indoor unit Model 50 or smaller 12.7 (1/2) Brazed
(19.05 (3/4) with optional joint pipe used.)
32 (1-1/4)
24 (53)
Drain Connection pipe (with flexible hose and insulation)
Reducer
CMB-PW202V-J
2
1N ~ 220/230/240V
50Hz
Galvanized steel plate
(Lower part drain pan painting N1.5)
PURY-(E)P200/250/300/350YJM-A(-BS)
PQRY-P200/250/300YHM-A
50% ~ 130% of outdoor unit/heat source unit
up to 130% of outdoor unit/heat source unit
up to 100% of outdoor unit/heat source unit
284 x 648 x 432 (11-3/16" x 25-9/16" x 17-1/16" )
Connectable outdoor unit capacity
P250/P300
ø19.05 (ø3/4" ) Brazed
ø22.2 (ø7/8" ) Brazed
Total down-stream Indoor unit capacity
P141~P200
P201~P300
ø9.52 (ø3/8" )
ø9.52 (ø3/8" )
Brazed
Brazed
ø19.05 (ø3/4" )
ø22.2 (ø7/8" )
Brazed
Brazed
O.D. 32mm (1-1/4" )
20 (45)
·Drain Connection pipe (with flexible hose and insulation)
·Refrigerant connection pipe
60Hz
0.054/0.061/0.067
0.024/0.027/0.030
0.25/0.27/0.28
0.11/0.12/0.13
Low press. pipe
19.05 (3/4)
Brazed
22.2 (7/8)
Brazed
28.58 (1-1/8)
Brazed
Gas pipe
bigger than 50 15.88 (5/8) Brazed
60Hz
Cooling : 0.018/0.019/0.019
Heating : 0.019/0.020/0.021
Cooling : 0.09/0.09/0.09
Heating : 0.09/0.09/0.09
P350
ø19.05 (ø3/4" ) Brazed
ø28.58 (ø1-1/8" ) Brazed
P301~P400
P401~
ø12.70 (ø1/2" )
ø15.88 (ø5/8" )
Brazed
Brazed
ø28.58 (ø1-1/8" )
ø28.58 (ø1-1/8" )
Brazed
Brazed