(5) Example of unt nstallaton

[Fig. IV. 3.(5).1]
(D)
(E)
(F)
(B)
(6) Insulaton nstallaton
The surface temperature of the water pipe would be very high, depending on the set temperature. Insulate the pipe
to prevent burns. When operating PWFY-P100, P200VM-E1-AU with cold water, insulate the water pipe to prevent
condensation.
Wrap insulation material around water pipes as shown in [Fig. IV. 3.(6).1].
Any heat source piping.
Indoor piping in cold-weather regions where frozen pipes are a problem.
When air coming from the outside causes condensation to form on piping.
Any drainage piping.
[Fig. IV. 3.(6).1]
(A)
(7) Flow swtch nstallaton
<Caution>
When installing the unit, be sure to install the supplied flow switch on the water outlet side of the unit and connect
the wire to IN1 of TB142A on the unit.
If the flow switch is not installed, the unit will emit the error signal (2100: Interlock error) and not operate.
* A short-circuit wire is supplied, but it is only for test run.
PWFY- P200VM-E1-AU
(C) (G)
(C)
(A)
(B)
(A)
(A) Close valve
(B) Water nlet
(C) Water outlet
(D) Refrgerant ppng
(G)
(E)
(B)
(A) Heat nsulaton materal (accessory)
(B) Inject wth caulkng materal
- 57 -
(E) Y-type strainer
(F) Dran ppe
(G) Expansion joint