(4) Refrgerant chargng calculaton (R2 system)

Sample connection (with 3 BC controller and 6 indoor units)
OU
(Main unit)
(Sub unit)
H
F
G
Reducer (P15-P50)
(attached with BC controller)
Amount of additional refrigerant to be charged
Refrigerant for extended pipes (field piping) is not factory-charged to the outdoor unit. Add an appropriate amount of refrigerant for each pipes on site.
Record the size of each high pressure pipe and liquid pipe, and the amout of refrigerant that was charged on the outdoor unit for future reference.
Calculating the amount of additional refrigerant to be charged
The amount of refrigerant to be charged is calculated with the size of the on-site-installed hige pressure pipes and liquid pipes, and their length.
Calculate the amount of refrigerant to be charged according to the formula below.
Round up the calculation result to the nearest 0.1kg. (i.e., 16.08 kg = 16.1 kg)
<Amount of additional refrigerant to be charged>
Calculating the amount of additional refrigerant to be charged
High pressure
Additional refrigerant
pipe size
charge
Total length of ø 28.58
=
(kg)
(m) x 0.36(kg/m)
Liquid pipe size
Total length of ø 15.88
+
(m) x 0.20(kg/m)
Total outdoor unit
Model
+
(E)P200
(E)P250 - (E)P500
(E)P550 - P900
Amount of factory charged refrigerant
Outdoor unit
Charged amount
Model
P200
EP200
9.5 kg
P250
P300
EP250
EP300
P350
11.8 kg
EP350
P400
P450
Limitation of the amount of refrigerant to be charged
The above calculation result of the amount of refrigerant to be charged must become below the value in the table below.
Outdoor unit model
P200
Maximum amount of
24.8kg
refrigerant *1
Outdoor unit model
EP200
Maximum amount of
27.3kg
refrigerant *1
*1 Amount of additional refrigerant to be charged on site
OU
Outdoor Twinning kit (High/Low press.)
CMY-R100VBK: Outdoor unit P400 (A1) to P650 / EP400 to EP600 (-A)
CMY-R200VBK: Outdoor unit P700 to P800 (-A)
CMY-R100XLVBK: Outdoor unit P800 (-A1) / EP600 (-A1) to EP700
CMY-R200XLVBK: Outdoor unit P850 and P900
The Low press. kit is set in the Main unit;
The High press. kit is to be installed in the field.
A
BC controller (Main BC)
a
b
CMY-R160-J1
(Joint)
IU
IU
2 : P250
1 : P50
High pressure
pipe size
Total length of ø 22.20
+
x 0.36
x 0.23
(m) x 0.23(kg/m)
Liquid pipe size
Total length of ø 12.7
+
x 0.2
x 0.12
(m) x 0.12(kg/m)
Charged amount per
Charged amount per
BC controller
BC controller
(Standard / Main)
(Main) HA-type
+
2.0 kg
2.0 kg
3.0 kg
5.0 kg
Sample calculation
Indoor
1: 80
A: ø28.58
2: 250
B: ø9.52
3: 32
C:
ø9.52
4: 40
D:
ø9.52
5: 32
E: ø9.52
6: 63
F: ø22.2
G: ø19.05
Outdoor
P550
P250
P300
P350
P400
33.8kg
34.8kg
39.7kg
46.7kg
EP250
EP300
EP350
EP400
34.0kg
35.0kg
39.7kg
47.5kg
CMY-Y202S-G2
CMY-Y102LS-G2
CMY-Y102SS-G2
(Joint)
C
CMY-Y102SS-G
(Joint)
B
c
d
IU
IU
3 : P15
4 : P20
High pressure
High pressure
pipe size
Total length of ø 19.05
Total length of ø 15.88
+
+
x 0.16
(m) x 0.16(kg/m)
Liquid pipe size
Liquid pipe size
Total length of ø 9.52
Total length of ø 6.35
+
+
x 0.06
(m) x 0.06(kg/m)
BC controller
Charged amount
(Sub) Total units
+
1 unit
1.0 kg
2 units
2.0 kg
The total length of each liquid line is as follows:
40m
a: ø9.52
10m
ø28.58: A = 40 m
ø22.2: F = 3 m
10m
b: ø9.52
5m
ø19.05: G = 1 m
20m
c: ø6.35
5m
ø9.52: C + D + E + a + b + f = 50 m
5m
d: ø6.35
10m
ø6.35: c + d + e = 20 m
5m
e: ø6.35
5m
Therefore,
3m
f: ø9.52
5m
<Calculation example>
1m
Additional refrigerant charge
= 40 × 0.36 + 3 × 0.23 + 1 × 0.16 + 50 × 0.06 + 20 × 0.024 + 5 + 2 + 5
= 30.8 kg
P450
P500
P550
P600
53.7kg
60.2kg
69.2kg
72.9kg
EP450
EP500
EP550
EP600
49.2kg
62.9kg
69.6kg
73.3kg
- 79 -
IU
e
5 : P140
BC controller (Sub BC)
D
BC controller (Sub BC)
E
f
IU
6 : P200
pipe size
x 0.11
(m) x 0.11(kg/m)
x 0.024
(m) x 0.024(kg/m)
Total capacity
of connected
Charged amount
+
indoor units
-80
2.0 kg
81 - 160
2.5 kg
161 - 330
3.0 kg
331 - 390
3.5 kg
391 - 480
4.5 kg
481 - 630
5.0 kg
631 - 710
6.0 kg
711 - 800
8.0 kg
801 - 890
9.0 kg
891 - 1070
10.0 kg
1071 - 1250
12.0 kg
1251 -
14.0 kg
P650
P700
P750
74.6kg
90.3kg
91.5kg
91.5kg
EP650
EP700
74.8kg
74.8kg
P800
P850
P900
91.5kg
91.5kg