Design And Installation Considerations; Locating Fireplace & Chimney - Heatilator LM42 Installation Manual

Woodburning fireplace
Hide thumbs Also See for LM42:
Table of Contents

Advertisement

B. Design and Installation Considerations
Consideration should be given to these factors before
deciding on a location.
NOTICE: Check building codes prior to installation.
• Installation MUST comply with local, regional, state and
national codes and regulations.
• Consult local building inspector, fire officials or authorities
having jurisdiction over restrictions, installation inspection
and permits.
Before installing, determine the following:
- Where the fireplace is to be installed.
- The chimney system configuration to be used.
- Facing, mantel, hearth construction and finishing
details.
-
Gas supply piping.
Location NOT recommended:
• Not the highest point of the roof
• Wind loading possible
Windward
Figure 2.2
Recommended Chimney Locations
6
Recommended Location:
• Above peak
Marginal Location:
• Below peak
Recommended:
• Insulated exterior chase
in cooler climates
Not recommended in basement due
to high negative pressure concerns
that effect draft
Heatilator • LM42 • Installers Manual • 4087-901 • Rev A • 04/14/16
1. Locating Fireplace & Chimney
Location of the fireplace and chimney will affect perfor-
mance.
• Install within the warm airspace enclosed by the building
envelope. This helps to produce more draft, especially
during lighting and die-down of the fire.
• Installing the fireplace in a basement is not recommended
due to negative pressure concerns.
Penetrate the highest part of the roof. This minimizes
the effects of wind loading.
Locate termination cap away from trees, adjacent
structures, uneven roof lines and other obstructions.
• Minimize the use of chimney offsets.
• Consider the fireplace location relative to floor and ceiling
and attic joists.
Take into consideration the termination requirements in
Sections 4 and 5.
Install the outside air kit with the intake facing prevailing
winds during the heating season.
Ensure adequate outdoor air for all combustion
appliances and exhaust equipment.
Ensure furnace and air conditioning return vents are not
located in the immediate vicinity of the fireplace.
• Avoid installing the fireplace near doors, walkways or
small isolated spaces.
• Recessed lighting should be a "sealed can" design.
Attic hatches weather stripped or sealed.
Attic mounted duct work and air handler joints and seams
taped or sealed.
Multi-level Roofs
Recommended Location:
• Above peak
• Inside heated space
Marginal Location:
• Wind loading possible
Location NOT recommended:
• Too close to tree
• Below adjacent structure
• Lower roof line
• Avoid outside wall
Leeward

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lm42-ss

Table of Contents