C. Termination Requirements
• Install a cap approved and listed for this fireplace system.
• Locate cap where it will not become plugged by snow or other materials.
Locate cap away from trees or other structures.
• The bottom of the termination cap must be at least 3 ft (.91 m) above the roof AND at least 2 ft (.61 m) above any portion
of roof within 10 ft (3.05 m).
Slanted Roofs
Chimney must
extend 3 ft (.9 m)
above the roof
Flat Roofs
Chimney must
extend 3 ft (.9 m)
above the roof
Figure 4.3
Multiple Chimney Locations
22
Heatilator • LM42 • Installers Manual • 4087-901 • Rev A • 04/14/16
Chimney must extend 2 ft (.6 m)
above any portion of the roof or
adjacent structures within
10 ft (3 m) of the chimney
Chimney must extend 2 ft (.6 m)
above any portion of the roof or
adjacent structures within
10 ft (3 m) of the chimney