Outdoor Unit Installation - Daikin FDYB-KA Series Engineering Data

Table of Contents

Advertisement

ED41-016B

15.1.11 Outdoor Unit Installation

〈 The following information is for RY35–50–60 outdoor unit types. Refer to the installation manual attached to the outdoor unit for other outdoor
unit types. 〉
〈 SELECTING INSTALLATION SITE 〉
Select an installation site where the following conditions are satisfied and that meets with your customer's approval.
• Places which are well–ventilated.
• Safe places which can withstand the unit's weight and vibration and where the unit can be installed level.
• Places where the unit does not bother next-door neighbors.
• Places where there is no possibility of flammable gas leak.
• Places where things distressed in water do not exist because water drains off the outdoor unit.
• Places where servicing space can be well ensured.
RY35
50 mm
or more
150 mm
or more
50 mm
or more
RY60
100 mm
or more
〈 INSTALLATION 〉
• In case of bad drainage, build frames with concrete blocks, etc. under the outdoor unit.
• To prevent the outdoor unit from falling or inclining from the frame, hang block strap around the hook or use turnbuckle.
A
FDYB-KA Series
100 mm
or more
50 mm
or more
150 mm or more
50 mm
300 mm or more
or more
100 mm
or more
100 mm
or more
100 mm
B
or more
H : The height of the
wall on the air
discharge side
B
Anchor bolt hole pitch
RY50
100 mm
or more
100 mm
or more
H: 1000 mm or less
H: 1000 mm or more
Use turnbuckle
(on suction grille side)
Installation
50 mm
or more
100 mm
or more
50 mm
or more
100 mm
or more
B dimension
350
600
MODEL
A
B
RY35
290
530
RY50
330
540
RY60
370
500
C : 3PN00281-18T-12
50 mm
or more
[mm]
63