Figure 6.5 Typical 100 Base-T Connection; Grounding-Plate Method - Fujitsu M10 Series Installation Planning Manual

Hide thumbs Also See for M10 Series:
Table of Contents

Advertisement

6.4.4

Grounding-plate method

In shared ground facilities complying with the International Electrotechnical
Commission (IEC) standards, noise generated by other electronic facilities such as
electronic devices, air conditioning facilities and elevators may penetrate the server
systems through the shared ground facilities' cables. In some cases, this can be
prevented by the grounding-plate method. In the grounding-plate method, a
grounding plate (see note below) is laid under the raised floor near the power
distribution panel, as shown in
equipment. For whether the site requires implementation of grounding-plate, consult
with the Facility section.
Note:
C120-H007-08EN

Figure 6.5 Typical 100 Base-T connection

Grounding-plate conducts by high-capacitance conductive sheet covering
over copper plate.
Figure
6.6. This reduces electrical noise from other
6.4 Grounding
81