(2) Distribution panel front plate
The front plate must be removable to allow for cable connection to the output terminal
boards.
(3) Connected device marking
A card holder is provided near each breaker to indicate the name of the associated
device.
(4) Output terminal boards requirements
The following list is output terminal board requirements:
Round crimp terminals must be connectable.
Screws should have a nominal metric screw head designation of M6, M8, or M10.
The correspondence between breakers and output terminal boards must be
identifiable.
The current rating of each output terminal board must be associated with the
corresponding breaker.
Output terminal boards must have the dimensions listed in
Breaker
rating
100 A
Round crimp terminal R38-10
is connectable
75 A
Round crimp terminal R22-8
is connectable
50 A
Round crimp terminal R14-6 is
connectable
30 A
Round crimp terminal R8-6 is
connectable
20 A
Round crimp terminal R8-6 is
connectable
C120-H007-08EN
Table 6.8 Output terminal board dimensions
Output terminal board
dimensions
Round crimp terminal dimensions
L
W
mm
in.
mm
41.5
1.634 22
33
1.299 16.5
29.5
1.161 12
23.5
0.925 12
23.5
0.925 12
6.5 Distribution Panels
Table
6.8.
d
in.
mm
in.
0.866 10.3
0.406
0.650 8.3
0.327
0.472 6.7
0.264
0.472 6.7
0.264
0.472 6.7
0.264
85