Table 6.4 Transformers Dedicated To 400 V Server Systems - Fujitsu M10 Series Installation Planning Manual

Hide thumbs Also See for M10 Series:
Table of Contents

Advertisement

b) Transformers dedicated to 400 V server systems
Table 6.4
dedicated to 400 V server systems and those that can be shared with other power
supplies.

Table 6.4 Transformers dedicated to 400 V server systems

Case
A dedicated high-to-low-voltage
transformer can be installed.
A high-to-low-voltage
transformer that is shared with
other power supplies.
C120-H007-08EN
describes the types of high-to-low-voltage transformers that can be
Transformer
dedicated to a server
system
Install a transformer in
the power receiving/
transformer room. If the
power receiving/
transformer room is not
close to the computer
room, install a separate
transformer near the
distribution panel in the
computer room.
The secondary terminal
of the separate
transformer shall be
grounded to a neutral
phase wire.
Install a separate
transformer near the
distribution panel in the
computer room, with its
secondary terminal
grounded to a neutral
phase wire.
6.2 Power Supply Facilities
Schematic view
High-voltage line
High-voltage line
71