Nx series constant and variable torque variable speed drives for induction motors
Hide thumbs Also See for NX series:
Table of Contents

Advertisement

4.3 Technical data
Mains
connection
Motor
connection
Control
characteristrics
Ambient
conditions
Table 4-2. Technical data (continues on next page)
Technical data
Input voltage U
208...240 V; 380...500 V; 525...690 V; -15%...+10%
in
Input frequency
45...66 Hz
Connection to mains
Once per minute or less (normal case)
Output voltage
0—U
Continuous output current
I
I
Starting torque
150% (Low overload); 200% (High overload)
Starting current
2.5 x I
and temperature of heatsink <+60ºC (up to 400 kW)
Output frequency
0...320 Hz (NXS); 7200 Hz (Special)
Frequency resolution
0.01 Hz (NXS); Application dependent (NXP)
Control method
Frequency Control U/f
Open Loop Sensorless Vector Control
Closed Loop Frequency Control
Closed Loop Vector Control (NXP only)
Switching frequency
Up to and including NX 0061:
(See parameter 2.6.9)
1...16 kHz; Factory default 10 kHz
From NX 0072:
1...10 kHz; Factory default 3.6 kHz
Frequency reference
Analogue input
Resolution 0.1% (10bit), accuracy ±1%
Panel reference
Resolution 0.01 Hz
Field weakening point
30...320 Hz
Acceleration time
0...3000 sec
Deceleration time
0...3000 sec
Braking torque
DC-brake: 30%*T
Ambient operating
–10ºC (no frost)... +50ºC: I
temperature
–10ºC (no frost)... +40ºC: I
Storage temperature
–40ºC...+70ºC
Relative humidity
0 to 95% RH, non-condensing, non-corrosive,
no dripping water
Air quality:
- chemical vapours
IEC 721-3-3, unit in operation, class 3C2
- mechanical particles
IEC 721-3-3, unit in operation, class 3S2
Altitude
100% load capacity (no derating) up to 1000m
1-% derating for each 100m above 1000m; max. 3000m
Vibration
5...200 Hz
(IEC 721-3-3, EN50178/
Displacement amplitude 3 mm at 5...10.7 Hz
EN60068-2-6, IEC68-2-6
Max acceleration amplitude 0.7 G at 10.7...200 Hz
(68-2-34, -35, -36)
Shock
UPS Drop Test (for applicable UPS weights)
EN50178, IEC 68-2-27
Storage and shipping: max 15 G, 11 ms (in package)
Enclosure class
IP21/NEMA1 standard in entire kW/HP range
IP54/NEMA12 option in entire kW/HP range
Note! Keypad installation required for IP54
in
: Ambient temperature max. +50ºC,
H
overload 1.5 x I
(1min/10min)
H
: Ambient temperature max. +40ºC,
L
overload 1.1 x I
(1min/10min)
L
2 secs every 20 secs, if output frequency <30Hz
H
(without brake option)
N
H
L
17(86)