Jumper block X1:
AI1 mode
A
B
C
AI1 mode: 0...20mA; Current input
A
B
C
AI1 mode: Voltage input; 0...10V
A
B
C
AI1 mode: Voltage input; 0...10V (differential)
A
B
C
AI1 mode: Voltage input; -10...10V
Jumper block X6:
AO1 mode
A
B
AO1 mode: 0...20mA; Current output
A
B
AO1 mode: Voltage output; 0...10V
= Factory default
Figure 6-20. Jumper selection for NXOPTA1
!
Check the correct positions of the jumpers. Running the motor
with signal settings different from the jumper positions will not
harm the frequency converter but may damage the motor.
WARNING
!
If the AI signal content is changed the corresponding board
parameter in
NOTE
Cabling and connections
D
D
D
AI2 mode: Voltage input; 0...10V (differential)
D
CMA and CMB grounding
C
D
C
D
menu M7
must also be changed.
Jumper block X2:
AI2 mode
A
B
C
D
AI2 mode: 0...20mA; Current input
A
B
C
D
AI2 mode: Voltage input; 0...10V
A
B
C
D
A
B
C
D
AI2 mode: Voltage input; -10...10V
Jumper block X3:
CMB connected to GND
CMA connected to GND
CMB isolated from GND
CMA isolated from GND
CMB and CMA
internally connected together,
isolated from GND
45(86)