Protection Control For Heating Operation - Panasonic WH-SDC12F6E5 Service Manual

Hide thumbs Also See for WH-SDC12F6E5:
Table of Contents

Advertisement

14.2

Protection Control for Heating Operation

14.2.1 Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid
compressor overloading.
14.2.2 Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor
stop.
Deice judging condition
Outdoor Unit Deice Control
10
5
0
-5
-10
-15
-20
-25
-30
-30
-20
Deice mode selection condition
There are 2 deice modes, according to water inlet temperature and outdoor ambient temperature the deice
o
mode is decided.
Water inlet temperature
50°C
27°C
Judgement details:
1) When water inlet temperature is more than 50°C, unit will operate deice mode 1.
2) When water inlet temperature is less than 27°C, unit will operate deice mode 2.
3) When water inlet temperature is less than 50°C and outdoor ambient temperature is less than -10°C, unit will
operate deice mode 2.
4) When water outlet temperature sensor 2 detect temperature is less than 22°C, unit will operate deice mode 2.
When Heating Time > 35 minutes
and Pipe Temperature below this
line for continuous 3 minutes
-10
0
Outdoor Temperature (°C)
Deice mode 1
Deice mode 2
-
10°C
10
20
97
Deice start depends:
1. Outdoor air sensor temp.
2. Outdoor pipe sensor temp.
3. Heating accumulation time
30
Outdoor ambient temperature