17.5.24
Output Over Current Detection (F23)
Malfunction Decision Conditions:
During operation of cooling and heating, when outdoor DC current is above 34 A is detected by the IPM DC Peak
sensing circuitry in the outdoor unit PCB (main).
Malfunction Caused:
1
Faulty outdoor unit PCB (main).
2
Faulty compressor.
Abnormality Judgment:
Continue for 7 times.
133