17.5.25
Refrigeration Cycle Abnormality (F24)
Malfunction Decision Conditions:
1
During operation of cooling and heating, compressor frequency > Frated.
2
During operation of cooling and heating, running current: 0.65 A < I < 1.65 A.
3
During operation of cooling, water inlet temperature - indoor refrigerant liquid temperature < 5°C.
4
During operation of heating, indoor refrigerant liquid temperature - water inlet temperature < 5°C.
Malfunction Caused:
1
Faulty water inlet or indoor refrigerant liquid temperature sensors.
2
2/3 way valve closed.
3
Refrigerant shortage (refrigerant leakage).
4
Clogged expansion valve or strainer.
5
Faulty outdoor unit PCB (main).
6
Poor compression of compressor.
Abnormality Judgment:
Continue 2 times in 20 minutes.
134