17.5.7 Water Flow Switch Abnormality (H62)
Malfunction Decision Conditions:
During operation of cooling and heating, the water flow detected by the indoor water flow switch is used to
determine water flow error.
Malfunction Caused:
1
Faulty water pump.
2
Water leak in system.
3
Faulty connector connection.
4
Faulty water flow switch.
5
Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 10 seconds (but no judgment for 9 minutes after compressor startup/restart).