17.5.10
Indoor Backup Heater OLP Abnormality (H70)
Malfunction Decision Conditions:
During operation of indoor backup heater, when no power supplies to indoor backup heater or OLP open circuit.
Malfunction Caused:
1
Faulty power supply connector connection.
2
Faulty connector connection.
3
Faulty indoor backup heater overload protector (OLP).
4
Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 60 seconds.