CONTROL SYSTEM
11.11.2
Outdoor Unit Controller
JP9 JUMPER LAYOUT
EEPROM Data (PIN 9)
GND
(PIN 10)
ODU MODEL SELECTION
ODU3
OFF
OFF
OFF
OFF
OFF
ON (PIN5 & PIN6)
OFF
ON (PIN5 & PIN6)
OFF
ON (PIN5 & PIN6)
OFF
ON (PIN5 & PIN6)
ON (PIN7 & PIN8)
ON (PIN7 & PIN8)
ON (PIN7 & PIN8)
ON (PIN7 & PIN8)
ON (PIN7 & PIN8)
ON (PIN5 & PIN6)
ON (PIN7 & PIN8)
ON (PIN5 & PIN6)
ON (PIN7 & PIN8)
ON (PIN5 & PIN6)
ON (PIN7 & PIN8)
ON (PIN5 & PIN6)
11.12
Test Mode
11.12.1
Entering Test Mode
System can enter Test mode in two ways:
•
Automatically when the following conditions exists for 30 minutes continuously:
o Mode = Cool, Set point = 16, Room temperature = 27±1, Outdoor temperature =
35±1
Or
o Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature =
7±1
•
Manually when entering diagnostics with the following settings:
•
o Mode = Cool, Set point = 16
o Mode = Heat, Set point = 30
11.12.2
Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed setting:
Indoor Fan Speed Setting
During test mode, protections are disabled, except for stop compressor status.
11-12
ODU3 (PIN 7)
ODU2 (PIN 5)
GND (PIN 8)
GND
ODU2
ODU1
OFF
OFF
OFF
OFF
OFF
ON (PIN3 & PIN4)
OFF
ON (PIN3 & PIN4)
OFF
OFF
ON (PIN3 & PIN4)
ON (PIN3 & PIN4)
OFF
OFF
OFF
OFF
OFF
ON (PIN3 & PIN4)
OFF
ON (PIN3 & PIN4)
OFF
OFF
ON (PIN3 & PIN4)
ON (PIN3 & PIN4)
Low
High
Auto
Revision Y05-01
CONTENT
ODU1 (PIN 3)
(PIN 6)
GND
(PIN 4)
ODU0
OFF
ON (PIN1 & PIN2)
OFF
ON (PIN1 & PIN2)
OFF
ON (PIN1 & PIN2)
OFF
ON (PIN1 & PIN2)
OFF
ON (PIN1 & PIN2)
OFF
ON (PIN1 & PIN2)
OFF
ON (PIN1 & PIN2)
OFF
ON (PIN1 & PIN2)
Unit Setting
Minimum Capacity Setting
Nominal Capacity Setting
Maximum Capacity Setting
Service Manual - Delta DCI
ODU0
(PIN 1)
GND
(PIN 2)
ODU Model
Reserved
A (Single DCR 20)
B (Single DCR 25)
C (Single DCR 35)
D
E (Duo DCI 50)
F
G
H
I
J
K
L
M
N
O