To Re-enter Programming Mode

1.
Key in 0 + ENTER + (engineer access code)
The panel starts bleeping once per second.
2.
Open the panel lid.
The panel bleeps twice and all the LEDs flash. The panel is now in program-
ming mode.
Restoring Default Engineer and User Codes
If you want to remove any programmed Engineer and User codes (perhaps to
reuse the panel with another user) then:
1.
Remove Mains supply.
2.
Open 601/602 lid and remove Battery supply.
Note: Leave the lid open and make sure the Lid Tamper switch does not
close, or this procedure will not work.
3.
On the 601: hold down OMIT and 9 and reconnect battery supply.
4.
On the 602: short together the two RST pins on the main pcb with a
small screwdriver and reconnect battery supply. Remove the screwdriver
after three seconds.
5.
Close lid and key in 1234.
22
496219 Issue 1