RED COMPACT 45 Installation Manual page 55

Pellet boiler
Table of Contents

Advertisement

12-SAFETY DEVICES AND ALARMS
ALARM SIGNALLING
When a condition occurs other than the one expected for regular operation of the boiler, an alarm is triggered.
The reason for the alarm is given on the control panel. The sound signal is not enabled for alarms A01-A02 in order not to disturb the user
when there is an absence of pellets in the night tank.
Panel signalling
A01
A02
A03
Thermostats alarm
A04
A05
Pressure switch alarm
A08
A09
A19
A20
Service
ALARM RESET
NEVER open the appliance door whilst the stove is either in the initial startup or on its shut down cycle, pellets will
still be smoldering or therefore volatiles may be present.
ATTENTION!
If during operation or initial ignition you encounter smoke spillage in to the room from the appliance or the flue
then please switch off the appliance, ventilate the room and contact the installation / service engineer immediately.
Technical Dept. - All rights reserved - Reproduction is prohibited
type of problem
The fire does not ignite.
The flame is extinguished unexpectedly.
The temperature of the pellet hopper or the
water temperature exceeds the safety threshold.
Smoke overtemperature
Fumes pressure switch intervention or water
pressure insufficient.
Anomalous operation of smoke fan.
Fault with the smoke sensor.
Fault with water sensor.
Puffer probe alarm.
Routine maintenance warning (does not seize) When this blinking message appears upon start-up, it
Solution
Check that the brazier is clean / the level of pellets in
the hopper.
Check the level of pellets in the tank.
Wait until the end of the cooling phase, stop the
alarm and re-ignite the boiler setting the supply of
fuel to minimum (SETTINGS menu - pellet recipe). If
the alarm persists, contact the service centre.
Check whether the room fan is working correctly (if
there is one).
The set smoke threshold has been exceeded. Reduce
the load of pellets (SETTINGS menu - Pellet recipe).
Check for chimney obstructions / door open or the
pressure of the hydraulic system.
If the alarm persists, contact the service centre.
If the alarm persists, contact the service centre.
Water sensor detached / interrupted / defective / not
recognised.
Puffer probe detached / interrupted / defective / not
recognised.
means it is time to carry out scheduled maintenance.
Call the assistance centre.
53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents