Performance Data; Calculation Steps - Daikin FT-J series Technical Manual

Split unit air conditioner wall mounted j & f series
Table of Contents

Advertisement

Performance Data

Calculation Steps

Interpolation method can be used to get the total
cooling capacity, TC and sensible cooling capacity,
SC and power input, PI at those temperatures which
are not stated out in the table. Extrapolation method
is not allowed to be used.
Example:
Model: FT10JXV1 – R09CXV1
Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 37°C DB
Fan Speed: High
1
st
Step
Interpolation of Indoor WB
Find TC, SC & PI
(a) Indoor: 25°C DB, 16°C WB
Outdoor: 35°C DB
(b) Indoor: 25°C DB, 19°C WB
Outdoor: 35°C DB
(c) Indoor: 25°C DB, 16°C WB
Outdoor: 40°C DB
(d) Indoor: 25°C DB, 19°C WB
Outdoor: 40°C DB
Details of Calculation:
1
st
Step:
To obtain the TC, SC & PI for
(a) Indoor Condition: 25°C DB, 16°C WB
Outdoor Condition: 35°C DB
EWB
EDB
24
16
25
27
2
nd
Step
Interpolation of Indoor DB
Find TC, SC & PI
(a) Indoor: 25°C DB, 17°C WB
Outdoor: 35°C DB
(b) Indoor: 25°C DB, 17°C WB
Outdoor: 40°C DB
Outdoor temperature
35°C
TC
SC
PI
3.20
3.20
1.27
x
y
z
1
1
1
3.30
3.30
1.27
Solution:
Based on the Performance Table,
1. Refer to the Indoor DB column,
-
25°C is located between 24°C & 27°C
for 16°C WB.
-
25°C is located between 24°C & 27°C
for 19°C WB.
-
Thus, Interpolation needs to be applied.
2. Refer to the Indoor WB column,
-
17°C is located between 16°C & 19°C
for 25°C DB.
-
Thus, Interpolation needs to be applied.
3. Refer to the Outdoor DB column,
-
37°C is located between 35°C & 40°C.
-
Thus, Interpolation needs to be applied.
3
rd
Step
Interpolation of Outdoor DB
Find TC, SC & PI
(a) Indoor: 25°C DB, 17°C WB
Outdoor: 37°C DB
By Interpolation Method
25°C – 24°C
=
27°C – 24°C
3.30kW – 3.20kW
⇒ x
= 3.23kW
1
Similarly,
y
= 3.23kW
1
z
= 1.27kW
1
Performance Data
x
– 3.20kW
1
22

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fty-f seriesFt-f seriesFty-j series

Table of Contents