Diagnostic Guidelines
By means of pressure readings:
Data
Circuit
High side
Low side
High side
Low side
High side
Low side
High side
Low side
High side
Low side
Pressure
Probable cause
1. Overcharged with refrigerant.
2. Non-condensable gases in refrigerant circuit (e.g. air).
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
1. Poor compression /no compression (compressor
defective)
2. Reversing valve leaking.
1. Undercharged with refrigerant.
2. Refrigerant leakage.
3. Air fi lter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
5. Defective defrost control, outdoor coil freeze up
(heating).
6. Outdoor fan locked / seized (heating).
1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
3. Indoor fan locked / seized (heating).
4. Indoor air fi lter clogged / dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air).
1. Air intake temperature of indoor unit too high.