Error Code - Panasonic CS-ME10DTEG Service Manual

Indoor - outdoor units
Hide thumbs Also See for CS-ME10DTEG:
Table of Contents

Advertisement

9.2.

Error Code

Symbol
Diagnosis
H11
Indoor / Outdoor
abnormal
communication
H12
Indoor unit capacity
unmatched
H14
Intake air temp.
sensor
H16
Outdoor Current
Transformer
H19
Indoor fan motor
mechanism lock
H21
Indoor float switch
abnormality
H23
Indoor heat exchanger
temp. sensor
H27
Outdoor air temp.
sensor
H28
Outdoor heat
exchanger temp.
sensor 1
This error occurs when indoor/outdoor unit communication fails to be established after 30 seconds or more.
<Diagnosis checkpoint>
1. Measure the voltage of the indoor/outdoor unit communication cables, and check whether the voltage is being
supplied properly to the outdoor unit or whether it is being returned from the outdoor unit to the indoor units.
This error occurs when wrong in the total connection capacity and wrong connection in each capacity.
The error is determined within 2 minutes after the power is turned on.
<Diagnosis checkpoint>
1. Check the total capacity of the units connected and check that the models are compatible for connection.
This error occurs when the intake air temperature has exceeded above 46°C continuously for 2 minutes or
dropped below -54°C continuously for 5 seconds during operation.
<Diagnosis checkpoint>
1. This error occurs when a temperature which is impossibly high or low from a normal standpoint has been
detected.
Check the sensor, and if open-circulating (more than 500k ohms) or short-circulating (less than 6.5k ohms)
is not found, defective contact of the connector is possible.
When the total current has dropped below the set current level continuously for 20 seconds during operation
beyond the set capacity, operation is stopped. Three minutes later, operation is started up again, and when the
trouble occurs on 4 successive occasions, the error occurs (the timer lamp blinks).
<Diagnosis checkpoint>
1. Check the refrigerating cycle: Gas may be leaking (the amount of refrigerant is extremely low).
2. Check the control P.C. Board: Check for a broken wire (open-circuit) in the current transformer. (If open-
circuit is found, replace the control P.C. Board.)
In the case of a scroll compressor (DC motor), H16 is detected only when the regular compressor is
operating.
• High-voltage PWM: When a state in which the fan motor speed is not synchronized with the control signal has
been detected on 7 successive occasions:
• Low-voltage PAM: When the fan lock detection signal has been detected on 7 successive occasions or it has
been detected continuously for 25 seconds or when a state in which the fan motor speed is not synchronized
with the control signal has been detected on 7 successive occasions:
The error occurs (the timer lamp blinks).
<Diagnosis checkpoint>
1. Check the nature of the fan lockup trouble.
2. Check for disconnections of the fan motor connectors and for defects in contact, in the fan motor and in the
control P.C. Board.
Error occurs when the float switch is open for 150 seconds.
<Diagnosis checkpoint>
1. Drain blockage
2. Check the conductivity of float switch.
3. Check that the resistance of the drain motor is about 200 ohms.
This error occurs when a temperature of under approximately -40°C or above approximately 80°C has been
detected by the heat exchanger temperature sensor continuously for 5 seconds.
(This error is not detected during de-icing.)
<Diagnosis checkpoint>
1. This error occurs when a temperature which is impossibly high or low from a normal standpoint has been
detected.
Check the sensor, and if open-circuit (more than 500k ohms) or short-circuit (less than 2.5k ohms) is not
found, defective contact of the connector or a defective control P.C. Board is possible.
This error occurs when a temperature of under approximately -40°C or above approximately 150°C has been
detected by the outdoor air temperature sensor for 2 to 5 seconds. (This error is not detected during de-icing.)
<Diagnosis checkpoint>
1. This error occurs when a temperature which is impossibly high or low from a normal standpoint has been
detected.
Check the sensor, and if open-circuit (more than 500k ohms) or short-circuit (less than 0.5k ohms) is not
found, defective contact of the connector or a defective control P.C. Board is possible.
This error occurs when a temperature of under approximately -60°C or above approximately 110°C has been
detected by the heat exchanger temperature sensor for 2 to 5 seconds. (This error is not detected during de-
icing.)
<Diagnosis checkpoint>
1. This error occurs when a temperature which is impossibly high or low from a normal standpoint has been
detected.
Check the sensor, and if open-circuit (more than 500k ohms) or short-circuit (less than 0.5k ohms) is not
found, defective contact of the connector or a defective control P.C. Board is possible.
Diagnosis method
92