• Under various setting mode, after select the transmission code combination of remote control, press any button of
remote control to transmit a signal to indoor unit. The transmission code will be stored in EEPROM.
• After signal is received, the various setting mode is cancelled and return to normal operation.
5. Individual setting mode
The H14 error detection selection mode is established by pressing the auto button about 21 seconds (5 beeps sound). Now
remove the remote control unit's battery cover, and short the "SET" terminals to established the beep sound mode.
*If the auto button is pressed and 26 seconds or so are allowed to elapse, the auto button operation mode is restored.
When nothing happens for 60 seconds in the "Setting mode", "Odour clear setting mode" or "Individual setting mode"
or if a remote control code is received, the mode concerned is canceled.
8.2.5.2.
Drain Test (SW1)
When installing the unit and you want the Drain pump to operate independently, press the DRAIN TEST switch to operate it for
about 5 minutes.
8.2.5.3.
High Static Pressure Switch (High state switch SW2)
To increase the fan speed, open the control box and the control board switch the HIGH STATE switch (SW2) to "HI".