Table (d): Indoor Air Temperature Shifting
1. Target room temperature shift value (dGetaDst)
• To offset the absolute gap between detection temperature with actual room temperature.
• The heat exchanger unit's temperature is different based on operation mode, it becomes the action operation mode
value.
2. Room temperature shift value (dGeta)
• When compressor ON/OFF, correction of detected room temperature by shift value during defrost etc.
i) Initial value when operation starts, or changing the actual operation mode.
Set the offset value at each operation mode. However, in order to improve the heating startup efficiency, the offset value
will be changed based on the gap between setting temperature and room temperature.
Actual operation mode
Cool
Heat
Soft Dry
ii) Updating during operation
During operation, it will compare with the target room temperature offset value at specific period, then the room
temperature will be updated.
Actual operation mode
Cool
Heat
Soft Dry
Update the room temperature offset value (dGeta)
Target room temp. offset value
Target room temp. offset value
Target room temp. offset value = Room temp. offset
However, if the following condition is occurred, temperature cannot detect correctly and therefore no updating will be
done.
• Heating zone E and above (Temperature gap is big and great capacity increased.)
• During deice
• After deice complete *within 600 sec.
• Comp. stop
Comp. starting *within 600 sec.
Table (e)
Installation position change heating shift
Actual operation mode
Cooling
Heating
Soft Dry
Gap between setting temperature and room temperature
(Operation start set temp. - room temp.)
(Operation start set temp.)
Room temperature zone
Temperature condition
Room temp. offset
value (dGetaDst
dGeta)
Room temp. offset
value (dGetaDst
dGeta)
value (dGetaDst = dGeta)
Target room temperature offset value (dGetaDst)
(1)
(2)
(0)
4°C
4°C
A, B, C, D zone
Room temp. offset value after modified (dGeta)
60
Room temperature offset value
(dGeta)
(0)
(4)
(4)
(0)
Updating period (sec.)
(180)
(15)
(180)
dGeta + (0.5)
dGeta - (0.5)
Do not change.
-4°C