8.4.1.3.
Cooling Operation
8.4.1.3.1.
Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
8.4.1.4.
Soft Dry Operation
8.4.1.4.1.
Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.0°C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
8.4.1.5.
Heating Operation
8.4.1.5.1.
Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < +2.0°C.
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.