Installing Chimney Components - Quadra-Fire EXPLR-I-MBK Installation Manual

Hide thumbs Also See for EXPLR-I-MBK:
Table of Contents

Advertisement

Solid Pack Chimney with Metal Supports as a Thimble
(Cont'd)
Min. Chimney Clearance to
Wall Spacer and
Combustibles - 2 inch (51mm)
Chimney Flue
Liner
Fireclay
Liner or
Equivalent
Masonry Chimney
Constructed to NFPA 211
Figure 13.1
Chimney Height / Rise and Run
This product was designed for and tested on a 6 inch (152mm)
chimney, 14 to 16 feet (420-480cm) high, (includes appliance
height) measured from the base of the appliance. The further
your stack height or diameter varies from this confi guration,
the greater the likelihood it may affect performance.
Chimney height may need to be increased by 2 - 3% per
each 1000 feet above sea level. It is not recommended to
use offsets or elbows at altitudes above 4000 feet above sea
level or when there are other factors that affect fl ue draft.
WARNING
Fire Risk.
Inspection of Chimney:
Chimney must be in good condition.
Meets minimum standard of NFPA 211
Factory-built chimney must be 6 inch (152mm) UL103 HT.
WARNING
Asphyxiation Risk.
• DO NOT CONNECT THIS Appliance TO A CHIM-
NEY FLUE SERVICING ANOTHER APPLIANCE.
• DO NOT CONNECT TO ANY AIR DISTRIBUTION
DUCT OR SYSTEM.
May allow fl ue gases to enter the house.
WARNING
Improper installation, adjustment, alteration, service or main-
tenance can cause injury or property damage. Refer to the
owner's information manual provided with this appliance. For
assistance or additional information consult a qualifi ed installer,
service agency or your dealer.
February 8, 2016
Min. Clearance
2 inch (51mm)
1 inch (25mm) Air
Space to Chimney
Section
Chimney
Connector
Chimney Section
Trim Collar
Wall Band
Wall Spacer
C. Installing Chimney Components
Chimney Connector
Single wall connector or appliance pipe.
This must be at least 24 gauge mild steel or 26 gauge blue
steel. The sections must be attached to the appliance and
to each other with the crimped (male) end pointing toward
the appliance. All joints, including the connection at the fl ue
collar, should be secured with 3 sheet metal screws. Make
sure to follow the minimum clearances to combustibles.
Where passage through the wall, or partition of combustible
construction is desired in Canada, the installation shall con-
form to CAN/CSA-B365.
Factory-built listed chimney connector (vented).
A listed connector (vented) must be used when installing
this appliance in a mobile home. The listed connectors must
conform to each other to ensure a proper fi t and seal.
Figure 13.2 Chimney Connector (Appliance Pipe)
Fire Risk.
Follow Chimney Connector Manufacturer's
Instructions for Proper Installation.
ONLY use connector:
Within the room, between appliance and ceiling or wall.
Connector shall NOT pass through:
Attic or roof space
Closet or similar concealed space
Floor or ceiling
Maintain minimum clearances to combustibles
7062-197B
Crimped
Flue Gas
End
Direction
Toward
Appliance
Secure pipe sections with a
minimum of 3 screws
WARNING
Explorer I
13