Functional Check - Siemens REV17 Series Instructions Manual

Hide thumbs Also See for REV17 Series:
Table of Contents

Advertisement

Access to the expert level
Set the program selection slider to RUN. Press
within 3 seconds press and hold down
3 seconds. This releases the engineering settings.
The display first shows language selection with Code 00. Press the buttons
Confirm settings by pressing
Press the operating mode selector
Code list
Function block
Code
00
Basic settings
01
02
10
LCD
11
optimization
12
30
Clock settings
31
32
Note 1:
Note 2:
Note 3:

Functional check

9 / 13
Siemens
Building Technologies
and
and
simultaneously for 3 seconds, release
.
to exit the engineering settings.
Name
Language
Sensor calibration
Switching differential 2-point
Illumination time
Background brightness
Contrast
Time zone
Deviation from time signal in Frankfurt
(Central European Time CET) (see Note 1)
Start of daylight saving time (see Note 2)
End of daylight saving time (see Note 3)
This entry has no effect if the radio clock either is inactive or not available.
The time signal received from Frankfurt is shifted by the value set in Code 30 (time zone)
if the radio clock is active.
The time is always changed over at 2 a.m. on the Sunday preceding the set date if there
is no radio clock or if it is inactive. The time change is shifted by the value set in Code 30
(time zone) when the radio clock is active.
The time is always changed over at 3 a.m. on the Sunday preceding the set date if there
is no radio clock or if it is inactive.
a)
Check the display. If there is no display, check insertion and function of the batteries.
b) Operating mode "Continuous comfort mode"
c)
Set the temperature setpoint higher than the displayed room temperature (see operating
instructions).
d)
The relay and, as a result, the actuating device must switch at the latest after one minute.
Symbol ▲ is displayed. If not displayed:
• Check actuating device and wiring.
• It is possible that in heating mode the room temperature is higher than the set
temperature setpoint.
e) Set the temperature setpoint for operating mode "Continuous comfort mode"
desired value.
f) Select the desired operating mode.
Room temperature controller REV17..
simultaneously for 3 seconds, release the buttons, and
is displayed.
or
Factory setting
English
off
0.5 °C
10 seconds
0
0
0 hours
31. March 31 (03-31)
31. October 31 (10-
31)
, read displayed temperature.
, and press
for another
to navigate the settings.
Your setting
CE1N2203en