Siemens REV17 Series Instructions Manual page 11

Hide thumbs Also See for REV17 Series:
Table of Contents

Advertisement

Technical data
General unit data
Standards
Product safety
Environmental conditions
Weight
Color
Size
11 / 13
Siemens
Building Technologies
Supply
Batteries (alkaline AA)
Life
Backup of clock when changing battery
(all other data remain in EEPROM)
Switching capacity of relay
Voltage
Current
Protection class
Sensing element
Measuring range
Time constant
Setpoint setting ranges
All temperature settings
Resolution for settings and displays
Setpoints
Switching times
Actual value measurement
Actual value display
Time display
CE conformity
Electromagnetic compatibility
Low voltage directive
C-tick
Automatic electrical controls for household
and similar use
Electromagnetic compatibility
Immunity
Emissions
Operation
Climatic conditions
Temperature
Humidity
Storage and transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Excl. packaging
Housing
Base
Housing with base
Room temperature controller REV17..
DC 3 V
2 x 1,5 V
Ca. 2 years
Max. 1 min
AC 24...250 V
0.1...6 (2.5) A
II as per EN 60 730-1
NTC 10 kΩ ±1 % at 25 °C
0...50 °C
Max. 10 min
3...35 °C
0.2 °C
10 min
0.1 °C
0.2 °C
1 min
2004/108/EEC
2006/95/EC
N474
EN 60 730-1
EN 61000-6-2
EN 61000-6-3
3K3 as per IEC 60 721-3
5...40 °C
<85 % r.h.
2K3 as per IEC 60 721-3
-25...70 °C
<93 % r.h.
2M2 as per IEC 60 721-3
0.29 kg
RAL9003 signal white
RAL7038 gray
90 x 134.5 x 30 mm
CE1N2203en
24.04.2008

Hide quick links:

Advertisement

Table of Contents
loading