Mitsubishi Electric MXZ-2D33VA Service Manual page 78

Hide thumbs Also See for MXZ-2D33VA:
Table of Contents

Advertisement

MXZ-4D72VA
R.V. coil
Refrigerant flow in cooling
OFF
ON
Refrigerant flow in heating
Indoor unit
D
Indoor unit
C
Indoor unit
B
Indoor unit
A
Indoor unit
A
Indoor unit
B
Indoor unit
C
Indoor unit
D
MAX REFRIGERANT PIPING LENGTH
Piping length each indoor unit (a, b, c, d)
Total piping length (a+b+c+d)
Bending point for each unit
Total bending point
It is irrelevant which unit is higher.
ADDITIONAL REFRIGERANT CHARGE
Outdoor unit
Refrigerant piping length (one way, 4 unit total)
precharged
40 m
(g)
2,700
0
Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 40)
WHEN CONNECTING TO MFZ-KJ SERIES INDOOR UNIT
MXZ-4D72VA -
/
E2
No. of
MFZ-KJ
indoor units
None
Charge-less (2,700 g)
1 unit
100 g additional charge (2,800 g)
2 units
200 g additional charge (2,900 g)
3 units
300 g additional charge (3,000 g)
4 units
400 g additional charge (3,100 g)
Refrigerant pipe diameter is different according to indoor unit to be
connected. When using extension pipes, refer to the right table.
When diameter of refrigerant pipe is different from that of outdoor
unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS
CATALOG".
OBH626K
High-pressure
switch
Oil separator
Stop valve with
service port
Muffler
Capillary tube
Strainer
LEV A
#100
Strainer
#100
LEV B
Strainer
#100
Strainer
LEV C
#100
LEV D
Strainer
#100
25 m
60 m
50 m
200
/
/
/
/
E3
ER2
ER3
ET2
ET3
Refrigerant piping length (L)
~ 40 m
Compressor
Discharge
temperature
thermistor RT62
Capillary tube
4-way valve
Stop valve
LEV E
Power
receiver
Indoor
units
25
60
60 m
400
~ 60 m
(L-40) x 20 g/m
100 g + (L-40) x 20 g/m
200 g + (L-40) x 20 g/m
300 g + (L-40) x 20 g/m
400 g + (L-40) x 20 g/m
78
Outdoor heat
exchanger
temperature
thermistor
RT68
Strainer
#100
Distributor
a
b
Outdoor
unit
c
d
Maximum amount of
refrigerant
3,100 g
3,200 g
3,300 g
3,400 g
3,500 g
UNIT: mm (inch)
Outdoor unit union diameter
For
Liquid
Indoor unit A
Gas
Liquid
Indoor unit B
Gas
Liquid
Indoor unit C
Gas
Liquid
Indoor unit D
Gas
UNIT: mm
FAN-OUT
Ambient
temperature
thermistor
RT65
Defrost
thermistor
RT61
Capillary tube
Max.
Height
difference
15 m
15 m
10 m
6.35(1/4)
12.7(1/2)
6.35(1/4)
9.52(3/8)
6.35(1/4)
9.52(3/8)
6.35(1/4)
9.52(3/8)