Mitsubishi Electric MXZ-2D33VA Service Manual page 135

Hide thumbs Also See for MXZ-2D33VA:
Table of Contents

Advertisement

MXZ-6D
Indication
No.
Symptom
LED1(Red) LED2(Yellow)
1
Outdoor
Lighted
unit does
not operate.
2
Lighted
3
Lighted
4
Lighted
5
Lighted
6
Lighted
7
Lighted
8
Lighted
9
Lighted
10
Lighted
11
Lighted
12
Lighted
13
Lighted
14 'Outdoor unit
stops and
restarts
Twice
3 minutes
later' is
repeated.
15
3 times
16
4 times
17
5 times
18
6 times
19
8 times
20
9 times
Not lighted
OBH626K
Abnormal point / Con-
dition
Once
LEV and drain pump
Outdoor power
Twice
system
Discharge temperature
3 times
thermistor
Fin temperature
thermistor
4 times
P. C. board tempera-
ture thermistor
Ambient temperature
thermistor
Outdoor heat ex-
changer temperature
5 times
thermistor
Defrost thermistor
Zero cross detecting
6 times
circuit (outdoor control
P.C. board)
7 times
Outdoor control system
8 times
Current sensor
Communication error
between P.C. boards
11 times
M-NET communication
error
Zero cross detecting
12 times
circuit (outdoor power
P.C. board)
13 times
Current sensor
14 times
Voltage sensor
15 times
Relay operation
IPM protection
Not lighted
Lock protection
Discharge temperature
Not lighted
protection
Fin temperature
protection
Not lighted
P.C. board temperature
protection
High-pressure
Not lighted
protection
Not lighted
Pre-heating protection
Not lighted
Converter protection
Bus-bar voltage
protection
Condition
The indoor unit detects an abnormality in the LEV
and drain pump.
Overcurrent protection cut-out operates 3 consecu-
tive times within 1 minute after the compressor
gets started, or converter protection cut-out or bus-
bar voltage protection cut-out operates 3 consecu-
tive times within 3 minutes after start-up.
A short circuit is detected in the thermistor during
operation, or an open circuit is detected in the
thermistor after 10 minutes of compressor start-up.
A short or open circuit is detected in the thermistor
during operation.
A short or open circuit is detected in the thermistor
during operation.
A short circuit is detected in the thermistor during
operation, or an open circuit is detected in the
thermistor after 5 minutes (in cooling) and 10
minutes (in heating) of compressor start-up.
A short circuit is detected in the thermistor during
operation, or an open circuit is detected in the
thermistor after 5 minutes of compressor start-up.
Zero cross signal can not be detected.
The nonvolatile memory data cannot be read
properly.
Current sensor protection cut-out operates 2 con-
secutive times.
The communication protection cut-out between
boards operates 2 consecutive times.
M-NET adapter P.C. board detects an abnormality
in the communication error.
The protection cut-out of the zero cross detecting
circuit operates 10 consecutive times.
A short or open circuit is detected in the input cur-
rent detection circuit during operation.
A short or open circuit is detected in the input volt-
age detection circuit during operation.
No relay operation is detected during operation.
Overcurrent is detected after 30 seconds of com-
pressor start-up.
Overcurrent is detected within 30 seconds of com-
pressor start-up.
The discharge temperature exceeds 116°C during
operation.
Compressor can restart if discharge temperature
thermistor reads 100°C or less 3 minutes later.
The fi n temperature exceeds during operation.
The P.C. board temperature exceeds during opera-
tion.
High-pressure is detected with the high-pressure
switch (HPS) during operation.
The outdoor heat exchanger temperature exceeds
70°C during cooling or the indoor gas pipe tem-
perature exceeds 70°C during heating.
Overcurrent is detected during pre-heating.
A failure is detected in the operation of the convert-
er during operation.
The bus-bar voltage exceeds 400 V or falls to low
level during compressor operating.
135
Remedy
• Refer to 11-6.
"Check of LEV".
• Check the drain pump of the indoor unit.
• Check the connection of the compressor connect-
ing wire.
• Refer to 11-6.
"How to check inverter/compres-
sor".
• Check the stop valve.
• Refer to 11-6.
"Check of outdoor thermistors".
• Refer to 11-6.
"Check of outdoor thermistors".
• Replace the outdoor control P.C. board.
• Refer to 11-6.
"Check of outdoor thermistors".
• Replace the outdoor control P.C. board.
• Replace the outdoor control P.C. board.
• Replace the outdoor power P.C. board.
• Check the connecting wire between outdoor con-
trol P.C. board and outdoor power P.C. board.
• Check the connecting wire between M-NET
adapter P.C. board and outdoor control P.C.
board, or terminal bed.
• Replace the outdoor power P.C. board.
• Replace the outdoor power P.C. board.
• Replace the outdoor power P.C. board.
• Replace the outdoor power P.C. board.
• Reconnect compressor connector.
• Refer to 11-6.
"How to check inverter/
compressor".
• Check the stop valve.
• Check the power module (PAM module).
• Check the amount of gas and refrigerant circuit.
• Refer to 11-6.
"Check of LEV".
•Check refrigerant circuit and refrigerant amount.
•Refer to 11-6.
"Check of outdoor fan motor".
• Check around of gas and the refrigerant circuit.
• Check the stop valve.
• Reconnect compressor connector.
• Refer to 11-6.
"How to check inverter/
compressor".
• Check the power module.
• Replace the outdoor power P.C. board.
• Check the voltage of power supply.
• Replace the outdoor power P.C. board or the out-
door control P.C. board.
• Refer to 11-6.
"Check of bus-bar voltage".

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents