Mitsubishi Electric MXZ-2D33VA Service Manual page 129

Hide thumbs Also See for MXZ-2D33VA:
Table of Contents

Advertisement

MXZ-6D
The left lamp of
OPERATION IN-
Abnormal point
DICATOR lamp
(Failure mode/protection)
(Indoor unit)
OFF
None (Normal)
2-time fl ash
Outdoor power system
3-time fl ash
Discharge temperature thermistor
Defrost thermistor
Ambient temperature thermistor
Fin temperature thermistor
P.C. board temperature thermis-
tor
Outdoor heat exchanger tem-
perature thermistor
4-time fl ash
Overcurrent
5-time fl ash
Discharge temperature
6-time fl ash
High pressure
7-time fl ash
Fin temperature
P.C. board temperature
8-time fl ash
Outdoor fan motor
9-time fl ash
Outdoor control system
10-time fl ash
Low discharge temperature
protection
11-time fl ash
Communication error
between P.C. boards
Current sensor
Zero cross detecting circuit
Converter
Bus-bar voltage
15-time fl ash
LEV and drain pump
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-4.).
OBH626K
LED indication
(Outdoor P.C.
board)
LED 1
LED 2
Lighted Lighted
Lighted Lighted Overcurrent protection cut-out operates 3 con-
secutive times within 1 minute after the com-
pressor gets started, or converter protection
cut-out or bus-bar voltage protection cut-out
operates 3 consecutive times within 3 minutes
after start-up.
Lighted
Once
A thermistor shorts or opens during
compressor running.
Lighted
Once
Lighted
Twice
Lighted 3 times
Lighted 4 times
Lighted 9 times
Once
Not
28 A current fl ows into power module.
lighted
Lighted Lighted The discharge temperature exceeds 116°C
during operation.
Compressor can restart if discharge tempera-
ture thermistor reads 100°C or less 3 minutes
later.
Lighted Lighted The outdoor heat exchanger temperature ex-
ceeds 70°C during cooling or the indoor gas pipe
temperature exceeds 70°C during heating.
3 times
Not
The fi n temperature exceeds 89°C during op-
lighted
eration.
4 times
Not
The P.C. board temperature exceeds 87°C
lighted
during operation.
Lighted Lighted A failure occurs 3 consecutive times within 30
seconds after the fan gets started.
Lighted 5 times Nonvolatile memory data cannot be read prop-
erly.
Lighted Lighted The frequency of the compressor is kept 80 Hz
or more and the discharge temperature is kept
under 39°C for more than 20 minutes.
Lighted 6 times Communication error occurs between the out-
door control P.C. board and outdoor power P.C.
board for more than 10 seconds.
The communication between boards protec-
tion cut-out operates 2 consecutive times.
Lighted 7 times A short or open circuit is detected in the cur-
rent sensor during compressor operating.
Current sensor protection cut-out operates 2
consecutive times.
5 times
Not
Zero cross signal cannot be detected while the
lighted
compressor is operating.
The protection cut-out of the zero cross
detecting circuit operates 10 consecutive
times.
5 times
Not
A failure is detected in the operation of the
lighted
converter during operation.
5 times
Not
The bus-bar voltage exceeds 400 V or falls to
lighted
low level during compressor operating.
Lighted Lighted The indoor unit detects an abnormality in
the LEV and drain pump.
129
Condition
• Check the compressor connecting
wire.
• Refer to 11-6.
verter/compressor".
• Check the stop valve.
• Refer to 11-6.
thermistors".
• Replace the outdoor control P.C.
board.
• Refer to 11-6.
thermistors".
• Reconnect compressor connector.
• Refer to 11-6.
verter/compressor".
• Check the stop valve.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-6.
• Check refrigerant circuit and refrig-
erant amount.
• Check the stop valve.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 11-6.
fan motor".
• Refer to 11-6.
fan motor".
• Replace the outdoor control P.C. board.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-6.
• Check the connecting wire between
outdoor control P.C. board and out-
door power P.C. board.
• Check the connecting wire among
outdoor control P.C. board and out-
door power P.C. board.
• Check the voltage of power supply.
• Replace the outdoor power P.C.
board.
• Check the voltage of power supply.
• Replace the outdoor control P.C.
board.
• Refer to 11-6.
• Check the drain pump of the indoor
unit.
Indoor/
outdoor unit
Remedy
failure mode
recall function
"How to check in-
"Check of outdoor
"Check of outdoor
"How to check in-
"Check of LEV".
"Check of outdoor
"Check of outdoor
"Check of LEV".
"Check of LEV".

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents