B) Your dealer may offer a liner fastening system (AC02006), sold separately. Follow the
installation instructions provided with the liner fastening system.

9.5.2 IF THE CHIMNEY LINER DOES NOT ALIGN WITH THE INSERT'S FLUE OUTLET

You can install a liner offset adapter (AC01370), which is sold separately. Please note that
an offset adaptor reduces the free flow of exhaust gases and may result in smoke roll-out
from the insert when its door is opened for loading. Only use an offset adaptor if a) there is
no other alternative and b) if the total height of the fireplace and chimney is at least 20
feet. If you must install a liner offset adapter, secure the three brackets with the three
screws provided (30131) on top of the insert in the three holes in front of the flue outlet.
The long end of the brackets must be attached to the insert. The brackets and screws are in
the insert's owner's manual kit. Then follow the instructions in the manual provided with
the liner offset adapter kit.
42 ______________________________________________________________________________