Calling Up Fault Codes From The Fault Memory (Fault History) - Viessmann VITOTRONIC 100 Installation And Service Instructions Manual

Table of Contents

Advertisement

Checking and acknowledging faults
Fault code System character-
istics
58
Cylinder primary
pump ON:
Set cylinder tem-
perature = Set boil-
er water
temperature, priority
control is cancelled
b1
Control mode
b4
Emissions test
mode
b5
Control mode
b6
Constant mode
b7
The boiler is regu-
lated by the control
thermostat
b9
Control mode
d1
Boiler cools down

Calling up fault codes from the fault memory (fault history)

The 10 most recent faults are saved
and may be scanned.
Faults are sorted by date. The most
recent fault is thus fault number 1.
(cont.)
Cause
Measures
Cylinder tempera-
Check cylinder tempera-
ture sensor lead
ture sensor
broken
(see page 50)
Communication
Check connections and
error, program-
replace the program-
ming unit
ming unit, if required
Internal fault
Check electronics PCB
Internal fault
Check electronics PCB
Invalid hardware
Check main PCB
recognised
Boiler coding card Plug in boiler coding
card or replace, if faulty
Internal fault
Acknowledge fault, re-
peat data input
Burner fault
Check the burner
1. Press G and d simultaneously
for approx. 2 s.
2. Call up individual fault codes with
b/ b.
3. Note
All saved fault codes can be
deleted with e.
Press d.
Troubleshooting
29