36 STANDARD CONTROLS ACCESS
Modes of Operation
The standby, parameter and information modes are accessible without the service code.
Standby Mode
S t b y
The standby mode will be shown after start up or reset of the boiler control module. If no buttons are pressed for 20 minutes
the display will automatically be set to standby mode. If new parameters have been stored they will then become active.
Parameter Mode
P A R A
In parameter mode it is possible to change the settings of the boiler control module. The following settings can be changed.
1. DHW Temperature
2. DHW System
3. CH System
4. Flow Temperature (T1)
Parameter settings and limits are listed below.
Parameter mode is entered from standby mode by pressing the 'mode' button once.
Press
Display
P A R A
Press the 'step' button until the desired parameter is displayed.
Press
Display
1. 6 0
2. 0 1
3. 0 1
4. 8 2
Press the '+' or '-' buttons to change the values.
The parameter setting can be stored by pressing and releasing the 'store' button, the new setting flashes twice to show it has
been accepted. The new setting will become active when the 'mode' button is pressed or if the display is left. If the display is
left, after 20 minutes it automatically returns to 'standby' mode.
-
Installation & Servicing
INSTALLATION
Description
DHW Temperature (ºC)
Instant water heater
Storage Tank
DHW System
00 = Off
01 = On
02 = Off + pump continuous
03 = On + pump continuous
CH System
00 = Off
01 = On
02 = Off + pump continuous
03 = On + pump continuous
CH Flow Temperature (ºC)
Lower
Upper
Factory
Limit
Limit
Setting
40
65
20
70
60
01
01
20
90
82
27